Overview

CHARACTERISTICS

Voltage Rating Uo/U

0.6/1kV

Temperature Rating

Fixed: -25°C to +90°C

Minimum Bending Radius

1.5mm2 to 16mm2 - Fixed: 12 x overall diameter

25mm2 and above - Fixed: 15 x overall diameter

Core Identification

2 core: Brown Blue

3 core: Brown Black Grey

3 core (optional) : Green/Yellow Blue Brown

4 core: Brown Black Blue Grey

4 core (optional) : Green/Yellow Brown Black Grey

5 core: Green/Yellow Brown Blue Black Grey

7 core and above: White cores with Black numbers

Sheath Colour

Black


STANDARDS

BS 5467, IEC/EN 60502-1, IEC/EN 60228

Flame Retardant according to IEC/EN 60332-1-2


Construction

Conductor

Class 2 stranded copper(AL) conductor

Insulation

XLPE (Cross-Linked Polyethylene)

Bedding

PVC (Polyvinyl Chloride)

Armour

SWA (Steel Wire Armour)

Sheath

PVC (Polyvinyl Chloride)


Parameter
Three core (CU) IEC 60502-1
Five core (CU) IEC 60502-1
Three core (AL) IEC 60502-1
Five core (AL) IEC 60502-1
CU conductor three core 0.6/1kV LV power cable standard IEC 60502-1(CU/XLPE/PVC/SWA/PVC)
NO./mm2Conductor NO.Insulation thickness (mm)Jacket thickness (mm)Diameter of cable(mm)CU weight
(kg/km)
Weight
of cable
(kg/km)
DC Resistance
(Ω/km)
Carrying capacity(A)
3*1.50.7 1.8 14.41 40.61 353.35 12.100 19 
3*2.50.7 1.8 15.39 67.68 413.57 7.410 25 
3*40.7 1.8 17.45 108.28 613.79 4.610 35 
3*60.7 1.8 18.69 162.42 721.32 3.080 45 
3*100.7 1.8 20.66 270.70 915.20 1.830 55 
3*160.7 1.8 23.68 433.12 1315.84 1.150 75 
3*250.9 1.8 27.31 676.75 1758.69 0.727 95 
3*350.9 1.9 28.93 947.45 2116.67 0.524 115 
3*5019 1.0 2.0 32.51 1353.50 2728.89 0.387 135 
3*7019 1.1 2.2 37.84 1894.90 3825.27 0.268 165 
3*9519 1.1 2.3 41.55 2571.65 4757.40 0.193 195 
3*12019 1.2 2.5 46.54 3248.41 6137.78 0.153 225 
3*15037 1.4 2.6 51.31 4060.51 7397.80 0.124 250 
3*18537 1.6 2.8 56.03 5007.96 8790.04 0.099 285 
3*24061 1.7 3.0 62.14 6496.81 10888.24 0.075 335 
3*30061 1.8 3.1 67.44 8121.02 13027.73 0.060 375 
3*40061 2.0 3.5 77.66 10828.02 17618.59 0.047 430 
3*50061 2.2 3.7 84.95 13535.03 21225.44 0.037 485 
CU conductor Five core 0.6/1kV LV power cable standard IEC 60502-1(CU/XLPE/PVC/SWA/PVC)
NO./mm2Conductor NO.Insulation thickness (mm)Jacket thickness (mm)Diameter of cable(mm)CU weight
(kg/km)
Weight
of cable
(kg/km)
DC Resistance
(Ω/km)
Carrying capacity(A)
5*1.50.7 1.8 16.91 67.68 553.76 12.100 19 
5*2.50.7 1.8 18.14 112.79 652.42 7.410 25 
5*40.7 1.8 19.59 180.47 783.51 4.610 35 
5*60.7 1.8 21.14 270.70 942.40 3.080 45 
5*100.7 1.8 24.30 451.17 1373.39 1.830 55 
5*160.7 1.8 27.20 721.87 1795.02 1.150 75 
5*250.9 2.0 32.13 1127.92 2490.97 0.727 95 
5*350.9 2.1 34.86 1579.09 3290.20 0.524 115 
5*5019 1.0 2.2 39.69 2255.84 4319.29 0.387 135 
5*7019 1.1 2.4 45.75 3158.17 5990.59 0.268 165 
5*9519 1.1 2.6 50.94 4286.09 7578.06 0.193 195 
5*12019 1.2 2.8 55.83 5414.01 9150.29 0.153 225 
5*15037 1.4 3.0 61.84 6767.51 11122.12 0.124 250 
5*18537 1.6 3.1 67.44 8346.60 13267.42 0.099 285 
5*24061 1.7 3.4 75.97 10828.02 17371.27 0.075 335 
5*30061 1.8 3.7 83.35 13535.03 21016.51 0.060 375 
5*40061 2.0 4.0 93.60 18046.70 26830.18 0.047 430 
5*50061 2.2 4.3 103.22 22558.38 32703.54 0.037 485 
AL conductor three core 0.6/1kV LV power cable standard IEC 60502-1(AL/XLPE/PVC/SWA/PVC)
NO./mm2Conductor NO.Insulation thickness (mm)Jacket thickness (mm)Diameter of cable(mm)CU weight
(kg/km)
Weight
of cable
(kg/km)
DC Resistance
(Ω/km)
Carrying capacity(A)
3*100.7 1.8 20.66 82.31 726.81 3.080 45 
3*160.7 1.8 23.68 131.69 1014.41 1.910 60 
3*250.9 1.8 27.31 205.77 1287.71 1.200 75 
3*350.9 1.9 28.93 288.07 1457.29 0.868 90 
3*5019 1.0 2.0 32.51 411.53 1786.92 0.641 105 
3*7019 1.1 2.2 37.84 576.14 2506.51 0.443 125 
3*9519 1.1 2.3 41.55 781.91 2967.66 0.320 155 
3*12019 1.2 2.5 46.54 987.68 3877.05 0.253 175 
3*15037 1.4 2.6 51.31 1234.60 4571.89 0.206 195 
3*18537 1.6 2.8 56.03 1522.67 5304.75 0.164 220 
3*24061 1.7 3.0 62.14 1975.35 6366.78 0.125 260 
3*30061 1.8 3.1 67.44 2469.19 7375.90 0.100 290 
3*40061 2.0 3.5 77.66 3292.25 10082.82 0.078 335 
3*50061 2.2 3.7 84.95 4115.32 11805.73 0.061 375 
AL conductor five core 0.6/1kV LV power cable standard IEC 60502-1(AL/XLPE/PVC/SWA/PVC)
NO./mm2Conductor NO.Insulation thickness (mm)Jacket thickness (mm)Diameter of cable(mm)CU weight
(kg/km)
Weight
of cable
(kg/km)
DC Resistance
(Ω/km)
Carrying capacity(A)
5*100.7 1.8 24.30 137.18 1059.40 3.080 45 
5*160.7 1.8 27.20 219.48 1292.63 1.910 60 
5*250.9 2.0 32.13 342.94 1705.99 1.200 75 
5*350.9 2.1 34.86 480.12 2191.23 0.868 90 
5*5019 1.0 2.2 39.69 685.89 2749.34 0.641 105 
5*7019 1.1 2.4 45.75 960.24 3792.66 0.443 125 
5*9519 1.1 2.6 50.94 1303.18 4595.16 0.320 155 
5*12019 1.2 2.8 55.83 1646.13 5382.41 0.253 175 
5*15037 1.4 3.0 61.84 2057.66 6412.26 0.206 195 
5*18537 1.6 3.1 67.44 2537.78 7458.61 0.164 220 
5*24061 1.7 3.4 75.97 3292.25 9835.50 0.125 260 
5*30061 1.8 3.7 83.35 4115.32 11596.80 0.100 290 
5*40061 2.0 4.0 93.60 5487.09 14270.57 0.078 335 
5*50061 2.2 4.3 103.22 6858.86 17004.03 0.061 375