Overview

Characteristics

Maximum operating voltage: 600 V.

Maximum operating temperature: 90 ° C in dry and humid environments.

Flame retardant.

Resistant to moisture, fat, and acid.

Available colors: black, white, red,

Blue, green, and yellow (caliber 14 to 8 AWG).

Black (calipers 6 AWG Y larger).


Standards

NTC 1332 UL 83


Construction

Solid annealed copper conductor or cable, insulated with XLPE.

Parameter
1C  600V LV power cable standard UL 83(CU/XLPE)
1C  600V LV power cable standard UL 83(CU/XLPE)
CalibreConductor Insulation thickness Diameter of cableWeight
of cable
Carrying capacity
AWG / kcmilmmmilsmminkg/kmlb/kftA
871,14455,980,23597,465,555
671,14456,890,27114698,375
471,14458,090,31822415095
271,14459,560,376344231130
1191,405510,90,429432290150
1/0191,405511,90,469539362170
2/0191,405513,00,511672452195
3/0191,405514,20,556838563225
4/0191,405515,60,6141048704260
250371,656517,60,6931249840290
300371,656519,00,74814891000320
350371,656520,20,79617291161350
400371,656521,40,84319661321380
500371,656523,50,92524421641430
600612,038026,21,0327581853475
750612,038029,61,1636682465535
1000612,038032,51,2848543262615