Overview

Characteristics 

High strength and low sag. Suitable for long-span line laying.

Construction

Heat-resistant aluminum alloy or annealed aluminum conductor, CFCC core support.

Parameter
HTLS CONDUCTOR - ALUMINUM CONDUCTOR FIBER REINFORCED
PRODUCT CODE121/17-FA-TT213/28-FA-TT267/37-FA-TT410/50-FA-TT492/55-FA-TT658/66-FA-TTT
(Equivalent conventional ACSR)(Dog equivalent)( Linnet Equivalent )( Panther Equivalent )(Grosbeak Equivalent )( Zebra Equivalent )(Moose Equivalent)
Mechanical Specifications
Overall Diameter of Conductor    mm1418.2920.7525.1528.1431.6
Nominal Aluminum Cross-sectional Area     mm2121.3212.7267.2407.18491.8657.7
Nominal Diameter of Composite Core (from CFCC data sheet)   mm5.36.87.899.510.4
Nominal Cross-sectional Area of Core     mm217.228.237.249.555.166.1
Nominal Cross-sectional Area of the Conductor    mm2138.5240.9304.3456.68546.94723.8
Ultimate Tensile Strength of Conductor      kN43.772.794.8129.1146.2179.1
Rated Strength of Core     kN36.860.379.5105.8117.7141.3
Core Nominal Mass per unit length       kg/km2744607886104
Aluminum Nominal Mass per unit length       kg/km335588738112413581819
Conductor Nominal Mass per unit length       kg/km362632798120214441923
Maximum Allowable Operating Temperature       °C180180180180180180
Coefficient of Linear Expansion Above Thermal Kneepoint     ×10-6/°C1.01.01.01.01.01.0
Coefficient of Linear Expansion Below Thermal Kneepoint     ×10-6/°C17.818.017.718.218.518.9
Final Modulus of Elasticity Above Thermal Kneepoint     GPa122122126126126126
Final Modulus of Elasticity Below Thermal Kneepoint     GPa63.3262.8563.6762.7362.1661.48
Electrical Specifications
Nominal Resistivity of Aluminium at 20°C, DC 63% IACS      ohm/km0.23070.13140.10470.06860.05680.0426
Current carrying capacity at maximum operating temperature@180 °C        Amps6749681127147616802009
Emergency operating temperature       °C200200200200200200