Overview

CHARACTERISTICS

Voltage Rating

6/10-18/30kV

Operating Temperature

Fixed: -40°C to +90°C

Flexed: 0°C to +90°C

Minimum Bending Radius

15 x overall diameter

Multiplex overhead service drop cables are resistant to weathering, abrasion, tearing, cutting and Chemicals.


Standards

IEC 60502, ICEA S-93 639, ICEA S-94 649


Construction

MV Aerial Bundled Conductor (ABC) Cables

Phase Conductor Circular compacted stranded H68 aluminium to BS2627.

Conductor Screen Extruded semi-conductive layer.

Insulation XLPE.

Insulation Screen Extruded semi-conductive layer.

metallic Screen(optional) Copper wire screen or copper tape screen.

Separator Semi-conductive swellable tape.

Outer Sheath HDPE.

Support Conductor Galvanized steel wires.

Assembly Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.


Parameter
3C MV AERIAL BUNDLED CABLE(ABC)
3C MV AERIAL BUNDLED CABLE(ABC)  12/20kV standard NFC 33-206  (AL/XLPE/CTS/HDPE+GSW/PE)
NO./mm2Min Conductor NO.Insulation thickness (mm)Cu tape thickness (mm)Messenger conductor (mm2)Diameter of cable(mm)AL weight
(kg/km)
Weight
of cable
(kg/km)
DC Resistance
(Ω/km)
3*255.5 0.12 50 58.70 205.77 2181.18 1.200 
3*355.5 0.12 50 60.07 288.07 2318.40 0.868 
3*5019 5.5 0.12 50 63.86 411.53 2598.52 0.641 
3*7019 5.5 0.12 50 68.04 576.14 2938.43 0.443 
3*9519 5.5 0.12 50 71.97 781.91 3304.77 0.320 
3*12019 5.5 0.12 50 75.90 987.68 3680.04 0.253 
3*15037 5.5 0.12 50 79.70 1234.60 4083.46 0.206 
3*18537 5.5 0.12 50 84.05 1522.67 4563.19 0.164 
3*24061 5.5 0.12 50 89.52 1975.35 5240.62 0.125 
3*30061 5.5 0.12 50 95.24 2469.19 5988.60 0.100 
3*40061 5.5 0.12 50 103.39 3292.25 7173.20 0.078 
3*50061 5.5 0.12 50 110.64 4115.32 8324.86 0.061 
3*63061 5.5 0.12 50 118.97 5185.30 9775.53 0.047