Overview

Characteristics

MECHANICAL PERFORMANCE

Minimum bending radius:x10 cable diameter

THERMINAL PERFORMANCE

Maximum service temperature:90°C

Maximum short-circuit temperature:250°C(max.5s)

Minimum service temperature.-40°


Standards

IEC 60502-1

ASTM B800  ASTM B 801  

ICEAS-95-658

UL 2556


Construction

1.Solid or stranded copper/aluminum conductor
2.Insulation with XLPE, PE, or PVC
3.For cables of two-phase or three-phase conductors, round or flat shape available
4.PVC inner COVERING
5.Concentric layer of helically layed copper/aluminum wires
6.Wrapping tape
7.Black XLPE, PE, or PVC jacket

Parameter
Copper conductor
Aluminnum Alloy conductor
Copper conductor(ASTM Standard)
N0.of AWGMin Conductor NO.φ Of Conductor(mm)Insulation thickness (mm)Neutral conductorJacket thickness (mm)Diameter of cable(mm)DC Resistance
(Ω/km)
mmNO.
2*1270.78 1.14 0.321391.14 7.74 5.430 
2*1070.981.14 0.511251.14 8.72 3.410 
2*871.231.14 0.643251.14 9.74 2.140 
2*671.551.14 0.813251.14 11.04 1.350 
2*471.961.14 1.02261.14 12.68 0.848 
8000 Aluminnum Alloy conductor(ASTM Standard)
N0.of AWGMin Conductor NO.φ Of Conductor(mm)Insulation thickness (mm)Neutral conductorJacket thickness (mm)Diameter of cable(mm)DC Resistance
(Ω/km)
mmNO.
2*1270.78 1.14 0.321391.14 7.74 8.880 
2*1070.981.14 0.511251.14 8.72 5.590 
2*871.231.14 0.643251.14 9.74 3.520 
2*671.551.14 0.813251.14 11.04 2.210 
2*471.961.14 1.02261.14 12.68 1.390